The AW-CFP2166 1 Zone series conventional fire alarm panel is designed based on EN54 part 2&4 standard. It is the heart of the fire automatic alarm system, which can realize centralized control, can supply power to the detectors, manual call point, bell etc.

5/5

Description

  • The AW-CFP2166 1 Zone fire alarm panel has the following characteristics:
    1. Analogue conventional detector inputs: 20 detectors or MCPs maximum.
    2. Smaller size and easier for installation, but all-around.
    3. Maximum number of bells per CIE: 4 Bells.
    4. 2 relay-outputs: FIRE/FAULT.
    5. High-capacity batteries: 12V2.3Ah*2, over 8h for stand-by use.
    6. Automatic power switchover: mains power and stand-by power.
    7. Succinct functional buttons: friendly user interface for easy operation and recognition.
    8. Fault supervision and notification: inputs, sounder, mains/batteries.
    9. Evacuation: man-made fire alarm condition on panel.
    10. Silence: sounders and panel buzzer.
    11. Extensible application for GSM: inform user anytime by mobile telephone.
  • AC INPUT 220VAC 50/60Hz +10%
    -15%
    DC OUTPUT 24VDC typical
    Voltage for MCU 5V
    Current @ 220VAC standby current ≤250mA
    Maximum current 1A
    Batteries current 750mA maximum, current limited
    Batteries 2*12V/ 2.3Ah sealed lead acid gel, self-regulated
    Battery low-voltage protection 22.2V
    The maximum and minimum electrical ratings for each input and output Detectots / zone lines: 21V-26V Sounder1 and sounder2 lines:21-26.2V
    Fire protection/Fire routing/Fault routing lines:21-26.2V
    Max points (detector and MCP) per CIE 20 detectors and 10 MCPs
    Zone alarm current 6mA minimum/ 27mA maximum
    Sounder output 2*0.3A maximum
    Relay contacts rating Dry contacts (NO/NC) 1A @24VDC
    EOL resistor for zone and outputs 6.8K 1W
    Fuse on EMI board 2A/ 250V Ceramic slow blow fuse 5*20(mm)
    Environmental Class A temperature range: -5 to 40°C (23~104°F)
    Humidity: 5 to 95% RH, non-condensing
    Terminal blocks rating All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2)
    Service life 10 years