DZ102S Addressable Strobe Sounder Base

The strobe sounder is designed with an upper cover and a lower
cover and installed on an independent base, it can be installed,
debugged and maintained conveniently.
It can realize electronic coding and rewrite the address via coder in situ.
It uses multiple super bright red LEDs as light sources for visual display, ensuring a striking display, a longer service life and low power consumption.
It is designed as fire detector base and strobe sounder together, can be connected with the fire detector model AS-ASD102,
AS-AHD105, AS-ASH107. The detector can be fixed by installing
above the strobe sounder base, thus realizing the linkage of the
alarm system.
Matched host machine: AS-MN3010, AS-9108E.

Parameters

Operating voltage: DC24V ± 20%
Quiescent current: ≤1mA; Alarm current: ≤130mA@DC24V
Operating temperature: -10℃~+55℃;
Relative humidity: ≤95% (40℃, without condensation)
Flushing rate: 1Hz~2Hz ;
Alarm volume: 75dB~120dB
Variable cycle: 4s-4.5s