SPECIAL FEATURES

  • Module Status by RED LED.
  • Analogue Communication with the panel.
  • Module Addressing by 8 way DIP switches.
  • Low Standby Current.
  • Available with suitable back boxes.

Electrical Specification

Operating Voltage : 24 VDC Nominal.
Alarm Current : 2.7 mA Max.(Latched)
Standby Current : 0.7 mA
Contact Rating : 2A @ 30VDC(Resistive)
End of Line Resistor : 47K Ohms
Communication Line

Loop Impedance

: 40 Ohms
IDC wiring Resistance : 1000 Ohms Max.
IDC Voltage : 8 V Max.
Temperature Range : 0°C to 49°C / 32°- 120°F
Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F.

Mechanical Specification

Dimensions : (95 W X 75 H X 24D) mm
Color : Black
Weight : 0.35 Kg

Compatible Devices

Model Description
Avani Analogue Addressable Fire Alarm Control Panel

Ordering Information

Model Description
RE – 717MX Analogue Addressable Input Output Module
    The input-output module (i o module) is a module with dual address settings with 8 digit dip switches, used to ingrate with a single third party system to monitor as well as control one independently. Shall have RED colored LED for status indications with supervisory features for input circuit.

 